Строка 157: |
Строка 157: |
| |} | | |} |
| | | |
− | Флаг Описание
| + | [https://wiki.it-kb.ru/apc/apc-nmc-oids-for-snmp-monitoring Источник] |
− | Flag 1 Abnormal Condition Present
| + | |
− | Flag 2 On Battery
| + | |
− | Flag 3 Low Battery
| + | |
− | Flag 4 On Line
| + | |
− | Flag 5 Replace Battery
| + | |
− | Flag 6 Serial Communication Established
| + | |
− | Flag 7 AVR Boost Active
| + | |
− | Flag 8 AVR Trim Active
| + | |
− | Flag 9 Overload
| + | |
− | Flag 10 Runtime Calibration
| + | |
− | Flag 11 Batteries Discharged
| + | |
− | Flag 12 Manual Bypass
| + | |
− | Flag 13 Software Bypass
| + | |
− | Flag 14 In Bypass due to Internal Fault
| + | |
− | Flag 15 In Bypass due to Supply Failure
| + | |
− | Flag 16 In Bypass due to Fan Failure
| + | |
− | Flag 17 Sleeping on a Timer
| + | |
− | Flag 18 Sleeping until Utility Power Returns
| + | |
− | Flag 19 On
| + | |
− | Flag 20 Rebooting
| + | |
− | Flag 21 Battery Communication Lost
| + | |
− | Flag 22 Graceful Shutdown Initiated
| + | |
− | Flag 23 Smart Boost or Smart Trim Fault
| + | |
− | Flag 24 Bad Output Voltage
| + | |
− | Flag 25 Battery Charger Failure
| + | |
− | Flag 26 High Battery Temperature
| + | |
− | Flag 27 Warning Battery Temperature
| + | |
− | Flag 28 Critical Battery Temperature
| + | |
− | Flag 29 Self Test In Progress
| + | |
− | Flag 30 Low Battery / On Battery
| + | |
− | Flag 31 Graceful Shutdown Issued by Upstream Device
| + | |
− | Flag 32 Graceful Shutdown Issued by Downstream Device
| + | |
− | Flag 33 No Batteries Attached
| + | |
− | Flag 34 Synchronized Command is in Progress
| + | |
− | Flag 35 Synchronized Sleeping Command is in Progress
| + | |
− | Flag 36 Synchronized Rebooting Command is in Progress
| + | |
− | Flag 37 Inverter DC Imbalance
| + | |
− | Flag 38 Transfer Relay Failure
| + | |
− | Flag 39 Shutdown or Unable to Transfer
| + | |
− | Flag 40 Low Battery Shutdown
| + | |
− | Flag 41 Electronic Unit Fan Failure
| + | |
− | Flag 42 Main Relay Failure
| + | |
− | Flag 43 Bypass Relay Failure
| + | |
− | Flag 44 Temporary Bypass
| + | |
− | Flag 45 High Internal Temperature
| + | |
− | Flag 46 Battery Temperature Sensor Fault
| + | |
− | Flag 47 Input Out of Range for Bypass
| + | |
− | Flag 48 DC Bus Overvoltage
| + | |
− | Flag 49 PFC Failure
| + | |
− | Flag 50 Critical Hardware Fault
| + | |
− | Flag 51 Green Mode/ECO Mode
| + | |
− | Flag 52 Hot Standby
| + | |
− | Flag 53 Emergency Power Off (EPO) Activated
| + | |
− | Flag 54 Load Alarm Violation
| + | |
− | Flag 55 Bypass Phase Fault
| + | |
− | Flag 56 UPS Internal Communication Failure
| + | |
− | Flag 57 Efficiency Booster Mode
| + | |
− | Flag 58 Off
| + | |
− | Flag 59 Standby
| + | |
− | Flag 60 Minor or Environment Alarm
| + | |
− | Идентификаторы OID, которые могут быть интересны для опроса по протоколу SNMP в целях инвентаризации.
| + | |
− | | + | |
− | Таблица 2. Идентификаторы OID из SNMPv2-MIB.
| + | |
− | | + | |
− | OID Name Описание
| + | |
− | 1.3.6.1.2.1.1.1.0 sysDescr A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software.
| + | |
− | 1.3.6.1.2.1.1.2.0 sysObjectID The vendor's authoritative identification of the network management subsystem contained in the entity
| + | |
− | 1.3.6.1.2.1.1.3.0 sysUpTime The time (in hundredths of a second) since the network management portion of the system was last re-initialized
| + | |
− | 1.3.6.1.2.1.1.4.0 sysContact The textual identification of the contact person for this managed node
| + | |
− | 1.3.6.1.2.1.1.5.0 sysName An administratively-assigned name for this managed node
| + | |
− | 1.3.6.1.2.1.1.6.0 sysLocation The physical location of this node
| + | |
− | 1.3.6.1.2.1.2.1.0 ifNumber The number of network interfaces present on this system
| + | |
− | Таблица 3. Идентификаторы OID из IF-MIB.
| + | |
− | | + | |
− | OID Name Описание
| + | |
− | 1.3.6.1.2.1.2.2.1.6.0.2 ifPhysAddress MAC Address in format «AB 00 AB 00 AB 00»
| + | |
− | Таблица 4. Идентификаторы OID из PowerNet-MIB.
| + | |
− | | + | |
− | OID Name Описание
| + | |
− | 1.3.6.1.4.1.318.1.1.1.1.1.1.0 upsBasicIdentModel APC UPS Model
| + | |
− | 1.3.6.1.4.1.318.1.1.1.1.1.2.0 upsBasicIdentName APC UPS Ident Name. An 8 byte ID string identifying the UPS
| + | |
− | 1.3.6.1.4.1.318.1.1.1.1.2.1.0 upsAdvIdentFirmwareRevision APC UPS Microcontroller Firmware Revision
| + | |
− | 1.3.6.1.4.1.318.1.1.1.1.2.2.0 upsAdvIdentDateOfManufacture APC UPS Manufacture Date in mm/dd/yy (or yyyy) format
| + | |
− | 1.3.6.1.4.1.318.1.1.1.1.2.3.0 upsAdvIdentSerialNumber APC UPS Serial Number. An 8-character string identifying the serial number of the UPS internal microprocessor
| + | |
− | 1.3.6.1.4.1.318.1.1.1.5.2.18.0 upsAdvConfigPositionSelector APC UPS Position. Configure UPS position selector. If the UPS doesn't support this configuration it will report unknown (1). The positions are either rack (2) for rack mounted or tower (3) for tower unit
| + | |
− | 1.3.6.1.4.1.318.1.1.1.7.2.7.0 upsAdvTestCalibrationDate APC UPS Last Runtime Calibration Date in mm/dd/yy format
| + | |
− | 1.3.6.1.4.1.318.1.1.1.2.1.3.0 upsBasicBatteryLastReplaceDate APC UPS Battery Last Replace Date in mm/dd/yy (or yyyy) format
| + | |
− | 1.3.6.1.4.1.318.1.1.1.2.2.5.0 upsAdvBatteryNumOfBattPacks APC UPS External Battery Packs Count
| + | |
− | 1.3.6.1.4.1.318.1.1.1.3.1.1.0 upsBasicInputPhase APC UPS AC Input Phase Count
| + | |
− | 1.3.6.1.4.1.318.1.1.1.2.2.6.0 upsAdvBatteryNumOfBadBattPacks APC UPS External Battery Packs Bad. The number of external battery packs connected to the UPS that are defective.
| + | |
− | 1.3.6.1.4.1.318.1.1.1.2.2.4.0 upsAdvBatteryReplaceIndicator APC UPS Battery Replace Indicator. Indicates whether the UPS batteries need replacing. Values: noBatteryNeedsReplacing (1), batteryNeedsReplacing (2)
| + | |
− | 1.3.6.1.4.1.318.1.1.1.7.2.6.0 upsAdvTestCalibrationResults APC UPS Last Runtime Calibration. The results of the last runtime calibration. Values: ok(1), invalidCalibration(2), calibrationInProgress(3)
| + | |
− | Таблица 5. Идентификаторы OID в PowerNet-MIB относятся к ветке experimental и не имеют имён (представленные здесь имена самодельные):
| + | |
− | | + | |
− | OID Name Описание
| + | |
− | 1.3.6.1.4.1.318.1.4.2.4.1.2.1 expNmcSerialNumber APC UPS Network Management Card Serial Number
| + | |
− | 1.3.6.1.4.1.318.1.4.2.4.1.4.1 expNmcAOSVersion APC UPS Network Management Card OS Version (AOS)
| + | |
− | 1.3.6.1.4.1.318.1.4.2.4.1.4.2 expNmcAppVersion APC UPS Network Management Card Application Module
| + | |
− | 1.3.6.1.4.1.318.1.4.2.4.1.3.1 expNmcAOSFile APC UPS Network Management Card OS (AOS) File
| + | |
− | 1.3.6.1.4.1.318.1.4.2.4.1.3.2 expNmcAppFile APC UPS Network Management Card Application Module File
| + | |
OID |
Name |
Описание
|
1.3.6.1.4.1.318.1.1.1.2.2.1.0 |
upsAdvBatteryCapacity |
APC UPS Battery Capacity (%)
|
1.3.6.1.4.1.318.1.1.1.2.2.3.0 |
upsAdvBatteryRunTimeRemaining |
APC UPS Battery Runtime Remaining (TimeTicks)
|
1.3.6.1.4.1.318.1.1.1.2.2.8.0 |
upsAdvBatteryActualVoltage |
APC UPS Battery Voltage (V DC)
|
1.3.6.1.4.1.318.1.1.1.3.2.1.0 |
upsAdvInputLineVoltage |
APC UPS Input Voltage (V AC)
|
1.3.6.1.4.1.318.1.1.1.5.2.2.0 |
upsAdvConfigHightransferVolt |
APC UPS Maximum Line Voltage (V AC)
|
1.3.6.1.4.1.318.1.1.1.5.2.3.0 |
upsAdvConfigLowTransferVolt |
APC UPS Minimum Line Voltage (V AC)
|
1.3.6.1.4.1.318.1.1.1.2.2.2.0 |
upsAdvBatteryTemperature |
APC UPS Internal Temperature (C)
|
1.3.6.1.4.1.318.1.1.1.4.2.3.0 |
upsAdvOutputLoad |
APC UPS Output Load (%) VA
|
1.3.6.1.4.1.318.1.1.1.4.2.1.0 |
upsAdvOutputVoltage |
APC UPS Output Voltage (V AC)
|
1.3.6.1.4.1.318.1.1.1.11.1.1.0 |
upsBasicStateOutputState |
APC UPS State Flags (ASCII String 64 flags)
|
Флаг |
Описание
|
Flag 1 |
Abnormal Condition Present
|
Flag 2 |
On Battery
|
Flag 3 |
Low Battery
|
Flag 4 |
On Line
|
Flag 5 |
Replace Battery
|
Flag 6 |
Serial Communication Established
|
Flag 7 |
AVR Boost Active
|
Flag 8 |
AVR Trim Active
|
Flag 9 |
Overload
|
Flag 10 |
Runtime Calibration
|
Flag 11 |
Batteries Discharged
|
Flag 12 |
Manual Bypass
|
Flag 13 |
Software Bypass
|
Flag 14 |
In Bypass due to Internal Fault
|
Flag 15 |
In Bypass due to Supply Failure
|
Flag 16 |
In Bypass due to Fan Failure
|
Flag 17 |
Sleeping on a Timer
|
Flag 18 |
Sleeping until Utility Power Returns
|
Flag 19 |
On
|
Flag 20 |
Rebooting
|
Flag 21 |
Battery Communication Lost
|
Flag 22 |
Graceful Shutdown Initiated
|
Flag 23 |
Smart Boost or Smart Trim Fault
|
Flag 24 |
Bad Output Voltage
|
Flag 25 |
Battery Charger Failure
|
Flag 26 |
High Battery Temperature
|
Flag 27 |
Warning Battery Temperature
|
Flag 28 |
Critical Battery Temperature
|
Flag 29 |
Self Test In Progress
|
Flag 30 |
Low Battery / On Battery
|
Flag 31 |
Graceful Shutdown Issued by Upstream Device
|
Flag 32 |
Graceful Shutdown Issued by Downstream Device
|
Flag 33 |
No Batteries Attachedц
|
Flag 34 |
Synchronized Command is in Progress
|
Flag 35 |
Synchronized Sleeping Command is in Progress
|
Flag 36 |
Synchronized Rebooting Command is in Progress
|
Flag 37 |
Inverter DC Imbalance
|
Flag 38 |
Transfer Relay Failure
|
Flag 39 |
Shutdown or Unable to Transfer
|
Flag 40 |
Low Battery Shutdown
|
Flag 41 |
Electronic Unit Fan Failure
|
Flag 42 |
Main Relay Failure
|
Flag 43 |
Bypass Relay Failure
|
Flag 44 |
Temporary Bypass
|
Flag 45 |
High Internal Temperature
|
Flag 46 |
Battery Temperature Sensor Fault
|
Flag 47 |
Input Out of Range for Bypass
|
Flag 48 |
DC Bus Overvoltage
|
Flag 49 |
PFC Failure
|
Flag 50 |
Critical Hardware Fault
|
Flag 51 |
Green Mode/ECO Mode
|
Flag 52 |
Hot Standby
|
Flag 53 |
Emergency Power Off (EPO) Activated
|
Flag 54 |
Load Alarm Violation
|
Flag 55 |
Bypass Phase Fault
|
Flag 56 |
UPS Internal Communication Failure
|
Flag 57 |
Efficiency Booster Mode
|
Flag 58 |
Off
|
Flag 59 |
Standby
|
Flag 60 |
Minor or Environment Alarm
|